esball

Products

406*282

CBX Bypass valve

The CBX discharge-bypass valve can automatically change the opening to get the constant outlet pressure on regardless of the change of the inlet pressure (within a certain range).

contact us
  • Technical Parameters
  • Accessories
  • Download

General

- The CBX discharge-bypass valve is a kind of load adjust component for the refrigerating system with a non-adjustable compressor.

- The CBX discharge-bypass valve can be used as automatic expansion valve under fixed pressure to maintain the fixed evaporation       pressure (temperature).

- The CBX discharge-bypass valve is capable of maintaining the minimum evaporating pressure.

- ODF connecting.

- Suitable for HFC and HCFC.

- Maximum working pressure: 45bar.


Characteristics


The main function of the CBX type bypass valve is that when the outlet pressure of the valve changes, the valve will automatically close or open, keeping the outlet pressure constant at the set value, and is not affected by the size of the inlet pressure (a certain range).


Other Technical Data



Note: Condensing temperature Te=3℃, evaporating temperature Tc=38℃; Refrigerant temperature ahead of valve: TL=37℃; Subcooling: Tsub=1k;


Pressure adjustment range and setting pressure




Dimensions